Steel Wire CATAFRACTATUS SWA Power Cable
Applicationem
Filum chalybeis cables armatae vel SWA cables est funis indutus durus ex Vagina Niger PVC, xlpe velit, conductores aeris et filum ferreum armatura.SWA Cables principales ad electricitatem destinatur ad retia subterranea, potestates retiaculorum ponenda, principalia ad domos advenientes inter multitudinem aliarum applicationum externe et interne.
Construction
Characteres
Conductor: Aluminium vel Copper
CATAFRACTATUS: SWA (Steel Wire Armoured)
Nulla: XLPE (polyethylene crucis coniunctum) aestimavit XC ° C
Cores: 1, 2, 3, 4, 5, 3+1, 4+1, 3+2
Sectio Area: 1.5mm2-300mm2
Packaging: Iron aut ligneus Drum
Signa
IEC 60502, BS 7870, GB/T12706
Morbi laoreet
2 Core Steel Wire Armored Cable | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Diae.Armatura filum | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
2x1.5 | 0.7 | 1 | 0.9 | 1.8 | 15 | 330 | 12.1 | 3.5 | 20 | 27 |
2x2.5 | 0.7 | 1 | 0.9 | 1.8 | 16 | 376 | 7.41 | 3.5 | 26 | 35 |
2x4 | 0.7 | 1 | 0.9 | 1.8 | 17 | 554 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1 | 0.9 | 1.8 | 18.2 | 633 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1 | 1.25 | 1.8 | 21 | 797 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1 | 1.6 | 1.8 | 23.5 | 1124 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1 | 1.6 | 1.8 | 26 | 1417 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1 | 1.6 | 1.8 | 30.5 | 1694 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1 | 1.6 | 1.8 | 27 | 1787 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1 | 1.6 | 2 | 30 | 2181 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.2 | 1.6 | 2.1 | 34 | 2768 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 1.2 | 2 | 2.2 | 36.5 | 3500 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 1.2 | 2 | 2.4 | 42 | 4233 | 0.124 | 3.5 | 325 | 345 |
2x185 |
| 1.2 | 2 | 2.5 | 45 | 4979 | 0.0991 | 3.5 | 375 | 390 |
3 Core Steel Wire Armored Cable | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Diae.Armatura filum | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3x1.5 | 0.7 | 1 | 0.9 | 1.8 | 15.8 | 359 | 12.1 | 3.5 | 20 | 27 |
3x2.5 | 0.7 | 1 | 0.9 | 1.8 | 16.8 | 415 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1 | 0.9 | 1.8 | 18 | 611 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1 | 0.9 | 1.8 | 19 | 718 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1 | 1.25 | 1.8 | 22 | 937 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1 | 1.6 | 1.8 | 24.5 | 1318 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1 | 1.6 | 1.8 | 29.2 | 1707 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1 | 1.6 | 1.8 | 32.5 | 2071 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1 | 1.6 | 1.9 | 33 | 2405 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1 | 1.6 | 2 | 37 | 3084 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 1.2 | 1.6 | 2.1 | 43 | 4126 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 1.2 | 2 | 2.3 | 45 | 4901 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 1.4 | 2 | 2.4 | 51 | 6365 | 0.124 | 3.5 | 325 | 345 |
3× 185 | 1.6 | 1.4 | 2 | 2.6 | 56 | 7555 | 0.0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 1.4 | 2.5 | 2.8 | 62 | 9284 | 0.093 | 3.5 | 440 | 450 |
3×300 | 1.8 | 1.6 | 2.5 | 3 | 67 | 11226 | 0.093 | 3.5 | 505 | 515 |
3×400 | 2 | 1.6 | 2.5 | 3.2 | 74 | 15714 | 0.047 | 3.5 | 570 | 575 |
4 Core Steel Wire Armored Cable | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Diae.Armatura filum | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 | 0.7 | 1 | 0.9 | 1.8 | 18 | 699 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1 | 1.25 | 1.8 | 19 | 820 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1 | 1.25 | 1.8 | 22 | 1233 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1 | 1.6 | 1.8 | 24.5 | 1550 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1 | 1.6 | 1.8 | 29.2 | 2036 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1 | 2 | 1.9 | 32.5 | 2501 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1 | 2 | 2 | 33 | 3064 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1 | 2 | 2.1 | 37 | 3974 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.2 | 2 | 2.3 | 43 | 5032 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 1.2 | 2.5 | 2.4 | 45 | 6327 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 1.4 | 2.5 | 2.5 | 51 | 7765 | 0.124 | 3.5 | 325 | 345 |
4× 185 | 1.6 | 1.4 | 2.5 | 2.7 | 56 | 9205 | 0.0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 1.4 | 2.5 | 3 | 62 | 11444 | 0.093 | 3.5 | 440 | 450 |
4×300 | 1.8 | 1.6 | 2.5 | 3.2 | 67 | 13830 | 0.093 | 3.5 | 505 | 515 |
4×400 | 2 | 1.6 | 3.15 | 3.5 | 74 | 19673 | 0.047 | 3.5 | 570 | 575 |
FAQ
Q: Possumusne nostrum logo vel societatis nomen imprimi in vestra producta vel in sarcina?
A: Ordo OEM & ODM vehementer gratus est et nos in inceptis OEM plene feliciter experimur.Quid amplius, nostra R&D turma dabit tibi suggestiones professionales.
Q: Quid mercedem verbis?
A: 30% T/T depositum, 70% T/T staterae solutionis ante shipment.
Q: Quomodo vestra officinam facit de qualitate potestate?
A: Arcam qualitatem temperantiae systematis habemus, et periti professionales nostros aspectum ac testium functionum omnium rerum nostrarum ante amet.
Q: Quomodo possum exemplum probare qualitatem tuam?
A: Libera exempla praebere possumus pro experimento et reprimendo, onera onera sustinenda iustus postulo.