CU/XLPE/PVC Steel Tape Armored Cable
Applicationem
Xlpe insulata pvc taenia armatae Cable ferro vaginata componitur ex puro conductore aeris, XLPE velit, armatura taenia ferro, et vagina PVC flammea retardat.Multicores funes industriales idonei sunt ad 0.6/1KV intentionis aestimationis, quae gravitati mechanicae sustinere possunt, quae adhiberi possunt ad stationes potentiarum, subway, cuniculos, aedificia alta surgunt, magna conatibus industrialibus et fodienda, agri olei, fodinis carbonis, et alia. loca intensiva retinacula electrica distributa.
Construction
Characteres
Ratum voltage: 0.6 / 1 kV
Maximum Conductor Temperature: sub normali (90℃), subitis (130℃) vel ambitu brevi non plus quam 5 condiciones (250℃).
Min.Ambient Temp.0℃, post institutionem et solum cum funem in certo situ
Min.Tendens Badius: 12 x cable OD pro multi core
Signa
IEC 60502-1, GB/T 12706.1
Morbi laoreet
2 CoreFerro Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
2x4 | 0.7 | 1.2 | 2x0.2 | 1.8 | 15 | 433 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.2 | 2x0.2 | 1.8 | 16 | 500 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.2 | 2x0.2 | 1.8 | 19 | 673 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.4 | 2x0.2 | 1.8 | 21 | 857 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.4 | 2x0.2 | 1.8 | 24 | 1173 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.6 | 2x0.2 | 1.8 | 25 | 1449 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.6 | 2x0.2 | 1.8 | 26 | 1877 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 2x0.2 | 1.8 | 27 | 2454 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 2x0.2 | 1.9 | 30 | 2483 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 2 | 2x0.2 | 2 | 33 | 4213 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 2 | 2x0.5 | 2.2 | 38 | 5087 | 0.124 | 3.5 | 325 | 345 |
III Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3x1.5 | 0.7 | 1 | 2x0.2 | 1.5 | 13 | 273 | 12.1 | 3.5 | 20 | 27 |
3x2.5 | 0.7 | 1 | 2x0.2 | 1.5 | 14 | 321 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.2 | 2x0.2 | 1.5 | 15 | 390 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.2 | 2x0.2 | 1.5 | 16 | 471 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.4 | 2x0.2 | 1.5 | 18 | 622 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.4 | 2x0.2 | 2 | 22 | 1005 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.6 | 2x0.2 | 2 | 25 | 1371 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.6 | 2x0.2 | 2 | 27 | 1724 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 2x0.2 | 2 | 30 | 2247 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 2x0.2 | 2.5 | 35 | 3023 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 2 | 2x0.5 | 2.5 | 39 | 3825 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 2x0.5 | 2.5 | 42 | 4642 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2 | 2x0.5 | 3 | 48 | 5767 | 0.124 | 3.5 | 325 | 345 |
3× 185 | 1.6 | 2.2 | 2x0.5 | 3 | 51 | 6895 | 0.0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.2 | 2x0.5 | 3 | 56 | 8617 | 0.093 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.2 | 2x0.5 | 3 | 59 | 10928 | 0.093 | 3.5 | 505 | 515 |
3×400 | 2 | 2.2 | 2x0.5 | 3.2 | 61 | 13556 | 0.047 | 3.5 | 570 | 575 |
IV Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 | 0.7 | 1 | 2x0.2 | 1.5 | 16 | 454 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1 | 2x0.2 | 1.5 | 17 | 557 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1 | 2x0.2 | 2 | 20 | 791 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1 | 2x0.2 | 2 | 23 | 1210 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1 | 2x0.2 | 2 | 27 | 1672 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1 | 2x0.2 | 2 | 29 | 2127 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1 | 2x0.2 | 2 | 33 | 2802 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.2 | 2x0.2 | 2.5 | 38 | 3785 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.2 | 2x0.5 | 2.5 | 42 | 4829 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 1.4 | 2x0.5 | 3 | 47 | 6033 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 1.4 | 2x0.5 | 3 | 52 | 7356 | 0.124 | 3.5 | 325 | 345 |
4× 185 | 1.6 | 1.6 | 2x0.5 | 3 | 56 | 8806 | 0.0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 1.6 | 2x0.5 | 3 | 62 | 11182 | 0.093 | 3.5 | 440 | 450 |
4×300 | 1.8 | 1.7 | 2x0.5 | 3.1 | 64 | 14176 | 0.093 | 3.5 | 505 | 515 |
4×400 | 2 | 1.7 | 2x0.5 | 3.5 | 69 | 17815 | 0.047 | 3.5 | 570 | 575 |
V Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
5×4 | 0.7 | 1 | 2x0.2 | 1.5 | 17.1 | 588 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1 | 2x0.2 | 1.5 | 19.4 | 720 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1 | 2x0.2 | 2 | 22.9 | 1014 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1 | 2x0.2 | 2 | 25.8 | 1392 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1 | 2x0.2 | 2 | 30.5 | 2002 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1 | 2x0.2 | 2 | 33.7 | 2581 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 1 | 2x0.5 | 2 | 38.6 | 3722 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 1.2 | 2x0.5 | 2.5 | 43.4 | 4897 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 1.2 | 2x0.5 | 2.5 | 48.6 | 6338 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 1.4 | 2x0.5 | 3 | 54.4 | 7851 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 1.4 | 2x0.5 | 3 | 60.1 | 9661 | 0.124 | 3.5 | 325 | 345 |
5× 185 | 1.6 | 1.6 | 2x0.5 | 3 | 66.7 | 11770 | 0.0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 1.6 | 2x0.5 | 3 | 74.7 | 14900 | 0.093 | 3.5 | 440 | 450 |
5×300 | 1.8 | 1.7 | 2x0.5 | 3.1 | 83.2 | 18000 | 0.093 | 3.5 | 505 | 515 |
III + I Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4 + 1×2.5 | 0.7 | 1 | 2x0.2 | 1.5 | 16 | 443 | 4.61 | 3.5 | 34 | 45 |
3×6 + 1×4 | 0.7 | 1 | 2x0.2 | 1.5 | 17 | 531 | 3.08 | 3.5 | 43 | 57 |
3×10 + 1×6 | 0.7 | 1 | 2x0.2 | 2 | 20 | 741 | 1.83 | 3.5 | 60 | 77 |
3×16 + 1×10 | 0.7 | 1 | 2x0.2 | 2 | 23 | 1135 | 1.15 | 3.5 | 83 | 105 |
3×25 + 1×16 | 0.9 | 1 | 2x0.2 | 2 | 26 | 1556 | 0.727 | 3.5 | 105 | 125 |
3×35 + 1×16 | 0.9 | 1 | 2x0.2 | 2 | 28 | 1896 | 0.524 | 3.5 | 125 | 155 |
3×50 + 1×25 | 1 | 1 | 2x0.2 | 2 | 31 | 2518 | 0.387 | 3.5 | 160 | 185 |
3×70 + 1×35 | 1.1 | 1.2 | 2x0.2 | 2.5 | 36 | 3293 | 0.268 | 3.5 | 200 | 225 |
3×95 + 1×50 | 1.1 | 1.2 | 2x0.5 | 2.5 | 40 | 4349 | 0.193 | 3.5 | 245 | 270 |
3×120 + 1×70 | 1.2 | 1.2 | 2x0.5 | 2.5 | 44 | 5365 | 0.153 | 3.5 | 285 | 310 |
3×150 + 1×70 | 1.4 | 1.4 | 2x0.5 | 3 | 49 | 6468 | 0.124 | 3.5 | 325 | 345 |
3×185 + 1×95 | 1.6 | 1.4 | 2x0.5 | 3 | 52 | 7854 | 0.0991 | 3.5 | 375 | 390 |
3×240 + 1×120 | 1.7 | 1.6 | 2x0.5 | 3.5 | 68 | 9814 | 0.093 | 3.5 | 440 | 450 |
3×300 + 1×150 | 1.8 | 1.7 | 2x0.5 | 3.5 | 71 | 12781 | 0.093 | 3.5 | 505 | 515 |
3×400 + 1×240 | 2 | 1.7 | 2x0.5 | 3.5 | 76 | 16359 | 0.047 | 3.5 | 570 | 575 |
3+2 Core Steel Tape Armored Cable | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4 + 2×2.5 | 0.7 | 1 | 2x0.2 | 1.5 | 17.5 | 855 | 4.61 | 3.5 | 34 | 45 |
3×6 + 2×4 | 0.7 | 1 | 2x0.2 | 1.5 | 18.9 | 1009 | 3.08 | 3.5 | 43 | 57 |
3×10 + 2×6 | 0.7 | 1 | 2x0.2 | 2 | 21.6 | 1461 | 1.83 | 3.5 | 60 | 77 |
3×16 + 2×10 | 0.7 | 1 | 2x0.2 | 2 | 24.6 | 1877 | 1.15 | 3.5 | 83 | 105 |
3×25 + 2×16 | 0.9 | 1 | 2x0.2 | 2 | 28.7 | 2583 | 0.727 | 3.5 | 105 | 125 |
3×35 + 2×16 | 0.9 | 1 | 2x0.2 | 2 | 30.7 | 3001 | 0.524 | 3.5 | 125 | 155 |
3×50 + 2×35 | 1 | 1 | 2x0.2 | 2 | 36.2 | 4392 | 0.387 | 3.5 | 160 | 185 |
3×70 + 2×35 | 1.1 | 1.2 | 2x0.2 | 2.5 | 40.3 | 5519 | 0.268 | 3.5 | 200 | 225 |
3×95 + 2×50 | 1.1 | 1.2 | 2x0.5 | 2.5 | 44.9 | 7543 | 0.193 | 3.5 | 245 | 270 |
3×120 + 2×70 | 1.2 | 1.2 | 2x0.5 | 2.5 | 50.3 | 9203 | 0.153 | 3.5 | 285 | 310 |
3×150 + 2×70 | 1.4 | 1.4 | 2x0.5 | 3 | 54 | 10485 | 0.124 | 3.5 | 325 | 345 |
3×185 + 2×95 | 1.6 | 1.4 | 2x0.5 | 3 | 60.2 | 13945 | 0.0991 | 3.5 | 375 | 390 |
3×240 + 2×120 | 1.7 | 1.6 | 2x0.5 | 3.5 | 67.2 | 15643 | 0.093 | 3.5 | 440 | 450 |
3×300 + 2×150 | 1.8 | 1.7 | 2x0.5 | 3.5 | 75.2 | 18204 | 0.093 | 3.5 | 505 | 515 |
IV + I Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 + 1×2.5 | 0.7 | 1 | 2x0.2 | 1.5 | 18.4 | 565 | 4.61 | 3.5 | 34 | 45 |
4×6 + 1×4 | 0.7 | 1 | 2x0.2 | 1.5 | 19.8 | 692 | 3.08 | 3.5 | 43 | 57 |
4×10 + 1×6 | 0.7 | 1 | 2x0.2 | 2 | 22.8 | 953 | 1.83 | 3.5 | 60 | 77 |
4×16 + 1×10 | 0.7 | 1 | 2x0.2 | 2 | 25.8 | 1318 | 1.15 | 3.5 | 83 | 105 |
4×25 + 1×16 | 0.9 | 1 | 2x0.2 | 2 | 30.4 | 1877 | 0.727 | 3.5 | 105 | 125 |
4×35 + 1×16 | 0.9 | 1 | 2x0.2 | 2 | 34.1 | 2324 | 0.524 | 3.5 | 125 | 155 |
4×50 + 1×25 | 1 | 1 | 2x0.2 | 2 | 38.7 | 3415 | 0.387 | 3.5 | 160 | 185 |
4×70 + 1×35 | 1.1 | 1.2 | 2x0.5 | 2.5 | 44.2 | 4432 | 0.268 | 3.5 | 200 | 225 |
4×95 + 1×50 | 1.1 | 1.2 | 2x0.5 | 2.5 | 49.8 | 5747 | 0.193 | 3.5 | 245 | 270 |
4×120 + 1×70 | 1.2 | 1.2 | 2x0.5 | 2.5 | 55.4 | 7112 | 0.153 | 3.5 | 285 | 310 |
4×150 + 1×70 | 1.4 | 1.4 | 2x0.5 | 3 | 60.1 | 8556 | 0.124 | 3.5 | 325 | 345 |
4×185 + 1×95 | 1.6 | 1.4 | 2x0.5 | 3 | 66.9 | 10510 | 0.0991 | 3.5 | 375 | 390 |
4×240 + 1×120 | 1.7 | 1.6 | 2x0.5 | 3.5 | 74.8 | 13232 | 0.093 | 3.5 | 440 | 450 |
4×300 + 1×150 | 1.8 | 1.7 | 2x0.5 | 3.5 | 78.4 | 16452 | 0.093 | 3.5 | 505 | 515 |
FAQ
Q: Possumusne nostrum logo vel societatis nomen imprimi in vestra producta vel in sarcina?
A: Ordo OEM & ODM vehementer gratus est et nos in inceptis OEM plene feliciter experimur.Quid amplius, nostra R&D turma dabit tibi suggestiones professionales.
Q: Quomodo societas tua facere de Quality Control?
A: 1) Totam materiam rudis qualitatem optimum delegimus.
2) Professionales & artifices periti curant singula in tractandis producendis.
3) Quality Control Department specially responsible for quality checking in each process.
Q: Quomodo possum exemplum probare qualitatem tuam?
A: Libera exempla praebere possumus pro probatione et inhibitione, iusta onera oneraria ferre necesse est.