CU/XLPE/PVC inermis
Applicationem
Funes pro electricitate copiae in humili intentione institutionis systematis adhibentur, aptae sunt ad institutionem in tectis et foris, in ductus funiculi, sub terra, in potestate et commutatione stationum, distributiones industriae locales, plantae industriales, ubi periculum mechanicae non est. damno.
Construction
Characteres
Ratum voltage: 0.6/1kV
1. Durante normali operatione funis, maxima conductor temperatus 70℃ pro insulatione PVC et 90" pro XLPE velit.
2.Maximum temperatura conductoris per ambitum brevem (maximam durationem non excedentem 5 seconds) : insulation PVC -- 160℃ pro conductor sectione transversalis ≤300mm2, 140℃ conductor sectioni transversalis > 300mm2;Nulla in PVC Crosslinked 250℃.
3. Cum retinacula ponatur, temperatus ambiens non erit minor quam 0℃, et radius minimus flexor licitus talis est:
Uno cable core: inermis 20D, armatus 15D
Funis multi-core: 15D pro inermis, 12D pro armatis
Qua: D- diametro funis exterioris actualis.
4.Cable vi fractionis:
Aluminium core cable: 40×S (N)
Funis aeris: 70×S (N)
Nota: S est totalis area crucis-sectionalis conductoris
Signa
IEC 60502-1, GB/T 12706.1
Morbi laoreet
Unius Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
1×1.5 | 0.7 | 1.4 | 6 | 53 | 12.1 | 3.5 | 22 | 33 |
1×2.5 | 0.7 | 1.4 | 6 | 68 | 7.41 | 3.5 | 31 | 43 |
1×4 | 0.7 | 1.4 | 7 | 87 | 4.61 | 3.5 | 41 | 56 |
1×6 | 0.7 | 1.4 | 7 | 110 | 3.08 | 3.5 | 52 | 70 |
1×10 | 0.7 | 1.4 | 8 | 155 | 1.83 | 3.5 | 71 | 94 |
1×16 | 0.7 | 1.4 | 9 | 220 | 1.15 | 3.5 | 92 | 120 |
1×25 | 0.9 | 1.4 | 10 | 345 | 0.727 | 3.5 | 120 | 155 |
1×35 | 0.9 | 1.4 | 12 | 424 | 0.524 | 3.5 | 150 | 185 |
1×50 | 1 | 1.4 | 13 | 555 | 0.387 | 3.5 | 180 | 220 |
1×70 | 1.1 | 1.4 | 14 | 770 | 0.268 | 3.5 | 230 | 270 |
1×95 | 1.1 | 1.5 | 16 | 1040 | 0.193 | 3.5 | 285 | 320 |
1×120 | 1.2 | 1.5 | 18 | 1290 | 0.153 | 3.5 | 335 | 365 |
1×150 | 1.4 | 1.6 | 20 | 1590 | 0.124 | 3.5 | 385 | 410 |
1×185 | 1.6 | 1.6 | 22 | 1944 | 0.0991 | 3.5 | 450 | 465 |
1×240 | 1.7 | 1.7 | 25 | 2510 | 0.093 | 3.5 | 535 | 540 |
1×300 | 1.8 | 1.8 | 27 | 3042 | 0.093 | 3.5 | 620 | 610 |
1×400 | 2 | 1.9 | 31 | 3869 | 0.047 | 3.5 | 720 | 695 |
1×500 | 2.2 | 2.1 | 35 | 4910 | 0.078 | 3.5 | 835 | 780 |
1×630 | 2.4 | 2.2 | 40 | 6220 | 0.093 | 3.5 | 960 | 880 |
1×800 | 2.6 | 2.4 | 45 | 7870 | 0.0218 | 3.5 | 1110 | 970 |
1×1000 | 2.8 | 2.6 | 51 | 9804 | 0.0176 | 3.5 | 1230 | 1060 |
2 Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
2×2.5 | 0.7 | 1.8 | 11.8 | 151 | 7.41 | 3.5 | 26 | 35 |
2×4 | 0.7 | 1.8 | 12.7 | 198 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.8 | 13.7 | 250 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.8 | 15 | 374 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.8 | 17 | 518 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.8 | 20 | 772 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.8 | 22 | 1006 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.8 | 20 | 1365 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 21 | 1872 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 24 | 2475 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 1.8 | 27 | 3089 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 1.9 | 30 | 3834 | 0.124 | 3.5 | 325 | 345 |
3 Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×1.5 | 0.7 | 1.5 | 10 | 145 | 12.1 | 3.5 | 20 | 27 |
3×2.5 | 0.7 | 1.5 | 11 | 185 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.5 | 12 | 250 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.5 | 13 | 320 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.8 | 16 | 450 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.8 | 18 | 640 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.8 | 21 | 940 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.8 | 23 | 1260 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 23 | 1670 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 26 | 2280 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 1.9 | 30 | 3020 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 32 | 3790 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2.2 | 37 | 4750 | 0.124 | 3.5 | 325 | 345 |
3× 185 | 1.6 | 2.3 | 41 | 5654 | 0.0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.4 | 46 | 7243 | 0.093 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.6 | 51 | 9465 | 0.093 | 3.5 | 505 | 515 |
3×400 | 2 | 3 | 64 | 12066 | 0.047 | 3.5 | 570 | 575 |
4 Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 | 0.7 | 1.8 | 13 | 253 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1.8 | 14 | 337 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1.8 | 17 | 501 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1.8 | 20 | 778 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1.8 | 23 | 1160 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1.8 | 25 | 1554 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1.8 | 23 | 2148 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.8 | 27 | 2928 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.9 | 31 | 3854 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 2 | 33 | 4925 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 2.2 | 38 | 6238 | 0.124 | 3.5 | 325 | 345 |
4× 185 | 1.6 | 2.3 | 42 | 7562 | 0.0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 2.5 | 47 | 9836 | 0.093 | 3.5 | 440 | 450 |
4×300 | 1.8 | 2.6 | 52 | 12550 | 0.093 | 3.5 | 505 | 515 |
4×400 | 2 | 3.1 | 66 | 15929 | 0.047 | 3.5 | 570 | 575 |
5 Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
5×4 | 0.7 | 1.8 | 14.5 | 349 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1.8 | 15.8 | 460 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1.8 | 19 | 699 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1.8 | 22 | 1013 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1.8 | 25 | 1566 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1.9 | 28 | 2083 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 2 | 31 | 2921 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 2.1 | 36 | 3974 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 2.2 | 39 | 5297 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 2.4 | 44 | 6638 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 2.5 | 49 | 8290 | 0.124 | 3.5 | 325 | 345 |
5× 185 | 1.6 | 2.7 | 55 | 10215 | 0.0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 3 | 64 | 13130 | 0.093 | 3.5 | 440 | 450 |
5×300 | 1.8 | 3.2 | 70 | 16670 | 0.093 | 3.5 | 505 | 515 |
III + I Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4+1×2.5 | 0.7 | 1.8 | 13 | 236 | 4.61 | 3.5 | 34 | 45 |
3×6+1/4 | 0.7 | 1.8 | 14 | 316 | 3.08 | 3.5 | 43 | 57 |
3×10+1×6 | 0.7 | 1.8 | 17 | 461 | 1.83 | 3.5 | 60 | 77 |
3×16+1×10 | 0.7 | 1.8 | 19 | 679 | 1.15 | 3.5 | 83 | 105 |
3×25+1×16 | 0.9 | 1.8 | 22 | 1065 | 0.727 | 3.5 | 105 | 125 |
3×35+1×16 | 0.9 | 1.8 | 24 | 1360 | 0.524 | 3.5 | 125 | 155 |
3×50+1×25 | 1 | 1.8 | 25 | 1901 | 0.387 | 3.5 | 160 | 185 |
3×70+1×35 | 1.1 | 1.9 | 28 | 2585 | 0.268 | 3.5 | 200 | 225 |
3×95+1×50 | 1.1 | 2 | 32 | 3518 | 0.193 | 3.5 | 245 | 270 |
3×120+1×70 | 1.2 | 2.1 | 35 | 4443 | 0.153 | 3.5 | 285 | 310 |
3×150+1×70 | 1.4 | 2.2 | 40 | 5326 | 0.124 | 3.5 | 325 | 345 |
3× 185+1×95 | 1.6 | 2.4 | 43 | 8501 | 0.0991 | 3.5 | 375 | 390 |
3× 240+1×120 | 1.7 | 2.5 | 48 | 11155 | 0.093 | 3.5 | 440 | 450 |
3×300+1×150 | 1.8 | 2.7 | 54 | 14470 | 0.093 | 3.5 | 505 | 515 |
3×400+1×240 | 2 | 3.1 | 66 | 309 | 0.047 | 3.5 | 570 | 575 |
3+2 Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4+2×2.5 | 0.7 | 1.8 | 13.9 | 413 | 4.61 | 3.5 | 34 | 45 |
3×6+2×4 | 0.7 | 1.8 | 15.3 | 6682 | 3.08 | 3.5 | 43 | 57 |
3×10+2×6 | 0.7 | 1.8 | 18 | 603 | 1.83 | 3.5 | 60 | 77 |
3×16+2×10 | 0.7 | 1.8 | 21 | 888 | 1.15 | 3.5 | 83 | 105 |
3×25+2×16 | 0.9 | 1.8 | 24 | 1342 | 0.727 | 3.5 | 105 | 125 |
3×35+2×16 | 0.9 | 1.8 | 26 | 1647 | 0.524 | 3.5 | 125 | 155 |
3×50+2×35 | 1 | 1.9 | 29 | 2386 | 0.387 | 3.5 | 160 | 185 |
3×70+2×35 | 1.1 | 2 | 32 | 3201 | 0.268 | 3.5 | 200 | 225 |
3×95+2×50 | 1.1 | 2.1 | 36 | 4269 | 0.193 | 3.5 | 245 | 270 |
3×120+2×70 | 1.2 | 2.3 | 41 | 5437 | 0.153 | 3.5 | 285 | 310 |
3×150+2×70 | 1.4 | 2.4 | 44 | 6519 | 0.124 | 3.5 | 325 | 345 |
3×185+2×95 | 1.6 | 2.5 | 49 | 8101 | 0.0991 | 3.5 | 375 | 390 |
3×240+2×120 | 1.7 | 2.7 | 54 | 10340 | 0.093 | 3.5 | 440 | 450 |
3×300+2×150 | 1.8 | 2.8 | 56 | 12810 | 0.093 | 3.5 | 505 | 515 |
IV + I Core Power Cable | ||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4+1×2.5 | 0.7 | 1.8 | 14.5 | 331 | 4.61 | 3.5 | 34 | 45 |
4×6+1/4 | 0.7 | 1.8 | 15.9 | 435 | 3.08 | 3.5 | 43 | 57 |
4×10+1×6 | 0.7 | 1.8 | 18 | 649 | 1.83 | 3.5 | 60 | 77 |
4×16+1×10 | 0.7 | 1.8 | 21 | 965 | 1.15 | 3.5 | 83 | 105 |
4×25+1×16 | 0.9 | 1.8 | 25 | 1456 | 0.727 | 3.5 | 105 | 125 |
4×35+1×16 | 0.9 | 1.8 | 27 | 1863 | 0.524 | 3.5 | 125 | 155 |
4×50+1×25 | 1 | 1.9 | 29 | 2633 | 0.387 | 3.5 | 160 | 185 |
4×70+1×35 | 1.1 | 2 | 32 | 3565 | 0.268 | 3.5 | 200 | 225 |
4×95+1×50 | 1.1 | 2.1 | 36 | 4735 | 0.193 | 3.5 | 245 | 270 |
4×120+1×70 | 1.2 | 2.3 | 41 | 5977 | 0.153 | 3.5 | 285 | 310 |
4×150+1×70 | 1.4 | 2.4 | 44 | 7276 | 0.124 | 3.5 | 325 | 345 |
4×185+1×95 | 1.6 | 2.5 | 49 | 9055 | 0.0991 | 3.5 | 375 | 390 |
4× 240+1×120 | 1.7 | 2.7 | 54 | 11567 | 0.093 | 3.5 | 440 | 450 |
4×300+1×150 | 1.8 | 3.1 | 66 | 14321 | 0.093 | 3.5 | 505 | 515 |
FAQ
Q: Possumusne nostrum logo vel societatis nomen imprimi in vestra producta vel in sarcina?
A: Ordo OEM & ODM vehementer gratus est et nos in inceptis OEM plene feliciter experimur.Quid amplius, nostra R&D turma dabit tibi suggestiones professionales.
Q: Quomodo societas tua facere de Quality Control?
A: 1) Totam materiam rudis qualitatem optimum delegimus.
2) Professionales & artifices periti curant singula in tractandis producendis.
3) Quality Control Department specially responsible for quality checking in each process.
Q: Quomodo possum exemplum probare qualitatem tuam?
A: Libera exempla praebere possumus pro experimento et reprimendo, onera onera sustinenda iustus postulo.