Bonus User Reputatio pro 0.6/1kv Yjv22 Yjv23 Yjlv22 Yjlv23 XLPE Insulata Steel Tape Subterranea Power Cable Armored
State-of-in arte instrumenta Comperto.Bona nostra in USA, in UK et sic deinceps exportantur, stante superbo inter consumentes pro bono User famae pro 0.6/1kv Yjv22 Yjv23 Yjlv22 Yjlv23 XLPE Steel Tape Armored Underground Power Cable Insulated, ex omnibus vitae spatiis amicissime excepit. ut mutuam cooperationem petant et cras splendidiorem et splendidiorem efficiant.
State-of-in arte instrumenta Comperto.Bona nostra ad USA, UK et sic porro, eximio stante inter usores proChina Control Cable and Single Core WireSocietas nostra operatur per principium operationis "integritatis fundatae, cooperationis creatae, homines ordinati, cooperationem vincere".Speramus nos amicitiam cum negotiatore ex toto orbe habere posse.
Applicationem
Xlpe insulata pvc taenia ferrata Cable ferro vaginata componitur ex puro conductore aeris, XLPE velit, armatura taenia ferro, et vagina PVC flammea retardat.Multicores funes industriales idonei sunt ad 0.6/1KV intentionis aestimationis, quae gravitati mechanicae sustinere possunt, quae adhiberi possunt ad stationes potentias, subway, cuniculos, aedificia alta ortum, magnas conatus industriales et fodiendi, agri oleum, fodinae carbones, aliaque alia. loca intensiva retinacula electrica distributa.
Construction
Characteres
Ratum voltage: 0.6 / 1 kV
Maximum Conductor Temperature: sub normali (90℃), subitis (130℃) vel ambitu brevi non plus quam 5 condiciones (250℃).
Min.Ambient Temp.0℃, post institutionem et solum cum funem in certo situ
Min.Tendens Badius: 12 x cable OD pro multi core
Signa
IEC 60502-1, GB/T 12706.1
Applicationem
linearum transmissio et distributio cum 50 Hz AC aestimata intentione Uo/U 0,6/1KV et infra portabuntur;Apta ad sepeliendum impositionem, non idonea ad pipelines impositio.
Morbi laoreet
2 CoreFerro Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
2×4 | 0.7 | 1.2 | 2×0.2 | 1.8 | 15 | 433 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.2 | 2×0.2 | 1.8 | 16 | 500 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.2 | 2×0.2 | 1.8 | 19 | 673 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.4 | 2×0.2 | 1.8 | 21 | 857 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.4 | 2×0.2 | 1.8 | 24 | 1173 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.6 | 2×0.2 | 1.8 | 25 | 1449 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.6 | 2×0.2 | 1.8 | 26 | 1877 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 2×0.2 | 1.8 | 27 | 2454 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 2×0.2 | 1.9 | 30 | 2483 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 2 | 2×0.2 | 2 | 33 | 4213 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 2 | 2×0.5 | 2.2 | 38 | 5087 | 0.124 | 3.5 | 325 | 345 |
III Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×1.5 | 0.7 | 1 | 2×0.2 | 1.5 | 13 | 273 | 12.1 | 3.5 | 20 | 27 |
3×2.5 | 0.7 | 1 | 2×0.2 | 1.5 | 14 | 321 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.2 | 2×0.2 | 1.5 | 15 | 390 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.2 | 2×0.2 | 1.5 | 16 | 471 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.4 | 2×0.2 | 1.5 | 18 | 622 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.4 | 2×0.2 | 2 | 22 | 1005 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.6 | 2×0.2 | 2 | 25 | 1371 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.6 | 2×0.2 | 2 | 27 | 1724 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 2×0.2 | 2 | 30 | 2247 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 2×0.2 | 2.5 | 35 | 3023 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 2 | 2×0.5 | 2.5 | 39 | 3825 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 2×0.5 | 2.5 | 42 | 4642 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2 | 2×0.5 | 3 | 48 | 5767 | 0.124 | 3.5 | 325 | 345 |
3× 185 | 1.6 | 2.2 | 2×0.5 | 3 | 51 | 6895 | 0.0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.2 | 2×0.5 | 3 | 56 | 8617 | 0.093 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.2 | 2×0.5 | 3 | 59 | 10928 | 0.093 | 3.5 | 505 | 515 |
3×400 | 2 | 2.2 | 2×0.5 | 3.2 | 61 | 13556 | 0.047 | 3.5 | 570 | 575 |
IV Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 | 0.7 | 1 | 2×0.2 | 1.5 | 16 | 454 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1 | 2×0.2 | 1.5 | 17 | 557 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1 | 2×0.2 | 2 | 20 | 791 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1 | 2×0.2 | 2 | 23 | 1210 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1 | 2×0.2 | 2 | 27 | 1672 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1 | 2×0.2 | 2 | 29 | 2127 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1 | 2×0.2 | 2 | 33 | 2802 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.2 | 2×0.2 | 2.5 | 38 | 3785 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.2 | 2×0.5 | 2.5 | 42 | 4829 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 1.4 | 2×0.5 | 3 | 47 | 6033 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 1.4 | 2×0.5 | 3 | 52 | 7356 | 0.124 | 3.5 | 325 | 345 |
4× 185 | 1.6 | 1.6 | 2×0.5 | 3 | 56 | 8806 | 0.0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 1.6 | 2×0.5 | 3 | 62 | 11182 | 0.093 | 3.5 | 440 | 450 |
4×300 | 1.8 | 1.7 | 2×0.5 | 3.1 | 64 | 14176 | 0.093 | 3.5 | 505 | 515 |
4×400 | 2 | 1.7 | 2×0.5 | 3.5 | 69 | 17815 | 0.047 | 3.5 | 570 | 575 |
V Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
5×4 | 0.7 | 1 | 2×0.2 | 1.5 | 17.1 | 588 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1 | 2×0.2 | 1.5 | 19.4 | 720 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1 | 2×0.2 | 2 | 22.9 | 1014 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1 | 2×0.2 | 2 | 25.8 | 1392 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1 | 2×0.2 | 2 | 30.5 | 2002 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1 | 2×0.2 | 2 | 33.7 | 2581 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 1 | 2×0.5 | 2 | 38.6 | 3722 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 1.2 | 2×0.5 | 2.5 | 43.4 | 4897 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 1.2 | 2×0.5 | 2.5 | 48.6 | 6338 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 1.4 | 2×0.5 | 3 | 54.4 | 7851 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 1.4 | 2×0.5 | 3 | 60.1 | 9661 | 0.124 | 3.5 | 325 | 345 |
5× 185 | 1.6 | 1.6 | 2×0.5 | 3 | 66.7 | 11770 | 0.0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 1.6 | 2×0.5 | 3 | 74.7 | 14900 | 0.093 | 3.5 | 440 | 450 |
5×300 | 1.8 | 1.7 | 2×0.5 | 3.1 | 83.2 | 18000 | 0.093 | 3.5 | 505 | 515 |
III + I Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4 + 1×2.5 | 0.7 | 1 | 2×0.2 | 1.5 | 16 | 443 | 4.61 | 3.5 | 34 | 45 |
3×6 + 1×4 | 0.7 | 1 | 2×0.2 | 1.5 | 17 | 531 | 3.08 | 3.5 | 43 | 57 |
3×10 + 1×6 | 0.7 | 1 | 2×0.2 | 2 | 20 | 741 | 1.83 | 3.5 | 60 | 77 |
3×16 + 1×10 | 0.7 | 1 | 2×0.2 | 2 | 23 | 1135 | 1.15 | 3.5 | 83 | 105 |
3×25 + 1×16 | 0.9 | 1 | 2×0.2 | 2 | 26 | 1556 | 0.727 | 3.5 | 105 | 125 |
3×35 + 1×16 | 0.9 | 1 | 2×0.2 | 2 | 28 | 1896 | 0.524 | 3.5 | 125 | 155 |
3×50 + 1×25 | 1 | 1 | 2×0.2 | 2 | 31 | 2518 | 0.387 | 3.5 | 160 | 185 |
3×70 + 1×35 | 1.1 | 1.2 | 2×0.2 | 2.5 | 36 | 3293 | 0.268 | 3.5 | 200 | 225 |
3×95 + 1×50 | 1.1 | 1.2 | 2×0.5 | 2.5 | 40 | 4349 | 0.193 | 3.5 | 245 | 270 |
3×120 + 1×70 | 1.2 | 1.2 | 2×0.5 | 2.5 | 44 | 5365 | 0.153 | 3.5 | 285 | 310 |
3×150 + 1×70 | 1.4 | 1.4 | 2×0.5 | 3 | 49 | 6468 | 0.124 | 3.5 | 325 | 345 |
3×185 + 1×95 | 1.6 | 1.4 | 2×0.5 | 3 | 52 | 7854 | 0.0991 | 3.5 | 375 | 390 |
3×240 + 1×120 | 1.7 | 1.6 | 2×0.5 | 3.5 | 68 | 9814 | 0.093 | 3.5 | 440 | 450 |
3×300 + 1×150 | 1.8 | 1.7 | 2×0.5 | 3.5 | 71 | 12781 | 0.093 | 3.5 | 505 | 515 |
3×400 + 1×240 | 2 | 1.7 | 2×0.5 | 3.5 | 76 | 16359 | 0.047 | 3.5 | 570 | 575 |
3+2 Core Steel Tape Armored Cable | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
3×4 + 2×2.5 | 0.7 | 1 | 2×0.2 | 1.5 | 17.5 | 855 | 4.61 | 3.5 | 34 | 45 |
3×6 + 2×4 | 0.7 | 1 | 2×0.2 | 1.5 | 18.9 | 1009 | 3.08 | 3.5 | 43 | 57 |
3×10 + 2×6 | 0.7 | 1 | 2×0.2 | 2 | 21.6 | 1461 | 1.83 | 3.5 | 60 | 77 |
3×16 + 2×10 | 0.7 | 1 | 2×0.2 | 2 | 24.6 | 1877 | 1.15 | 3.5 | 83 | 105 |
3×25 + 2×16 | 0.9 | 1 | 2×0.2 | 2 | 28.7 | 2583 | 0.727 | 3.5 | 105 | 125 |
3×35 + 2×16 | 0.9 | 1 | 2×0.2 | 2 | 30.7 | 3001 | 0.524 | 3.5 | 125 | 155 |
3×50 + 2×35 | 1 | 1 | 2×0.2 | 2 | 36.2 | 4392 | 0.387 | 3.5 | 160 | 185 |
3×70 + 2×35 | 1.1 | 1.2 | 2×0.2 | 2.5 | 40.3 | 5519 | 0.268 | 3.5 | 200 | 225 |
3×95 + 2×50 | 1.1 | 1.2 | 2×0.5 | 2.5 | 44.9 | 7543 | 0.193 | 3.5 | 245 | 270 |
3×120 + 2×70 | 1.2 | 1.2 | 2×0.5 | 2.5 | 50.3 | 9203 | 0.153 | 3.5 | 285 | 310 |
3×150 + 2×70 | 1.4 | 1.4 | 2×0.5 | 3 | 54 | 10485 | 0.124 | 3.5 | 325 | 345 |
3×185 + 2×95 | 1.6 | 1.4 | 2×0.5 | 3 | 60.2 | 13945 | 0.0991 | 3.5 | 375 | 390 |
3×240 + 2×120 | 1.7 | 1.6 | 2×0.5 | 3.5 | 67.2 | 15643 | 0.093 | 3.5 | 440 | 450 |
3×300 + 2×150 | 1.8 | 1.7 | 2×0.5 | 3.5 | 75.2 | 18204 | 0.093 | 3.5 | 505 | 515 |
IV + I Core Steel Tape Cable armatae | ||||||||||
Nom.Crucem-sectione conductor | Insulation Crassitudo | Interiorem covering Crassitudo | Ferro Tape Crassitudo | Vagina Crassitudo | Proxime.OD | Proxime Pondus | Maximilianus.DC Resistentia Conductoris (20°C) | Test intentione AC | Current Rating | |
mm2 | mm | mm | mm | mm | mm | kg/km | Ω/km | kV/5min | In aere (A) | In solo (A) |
4×4 + 1×2.5 | 0.7 | 1 | 2×0.2 | 1.5 | 18.4 | 565 | 4.61 | 3.5 | 34 | 45 |
4×6 + 1×4 | 0.7 | 1 | 2×0.2 | 1.5 | 19.8 | 692 | 3.08 | 3.5 | 43 | 57 |
4×10 + 1×6 | 0.7 | 1 | 2×0.2 | 2 | 22.8 | 953 | 1.83 | 3.5 | 60 | 77 |
4×16 + 1×10 | 0.7 | 1 | 2×0.2 | 2 | 25.8 | 1318 | 1.15 | 3.5 | 83 | 105 |
4×25 + 1×16 | 0.9 | 1 | 2×0.2 | 2 | 30.4 | 1877 | 0.727 | 3.5 | 105 | 125 |
4×35 + 1×16 | 0.9 | 1 | 2×0.2 | 2 | 34.1 | 2324 | 0.524 | 3.5 | 125 | 155 |
4×50 + 1×25 | 1 | 1 | 2×0.2 | 2 | 38.7 | 3415 | 0.387 | 3.5 | 160 | 185 |
4×70 + 1×35 | 1.1 | 1.2 | 2×0.5 | 2.5 | 44.2 | 4432 | 0.268 | 3.5 | 200 | 225 |
4×95 + 1×50 | 1.1 | 1.2 | 2×0.5 | 2.5 | 49.8 | 5747 | 0.193 | 3.5 | 245 | 270 |
4×120 + 1×70 | 1.2 | 1.2 | 2×0.5 | 2.5 | 55.4 | 7112 | 0.153 | 3.5 | 285 | 310 |
4×150 + 1×70 | 1.4 | 1.4 | 2×0.5 | 3 | 60.1 | 8556 | 0.124 | 3.5 | 325 | 345 |
4×185 + 1×95 | 1.6 | 1.4 | 2×0.5 | 3 | 66.9 | 10510 | 0.0991 | 3.5 | 375 | 390 |
4×240 + 1×120 | 1.7 | 1.6 | 2×0.5 | 3.5 | 74.8 | 13232 | 0.093 | 3.5 | 440 | 450 |
4×300 + 1×150 | 1.8 | 1.7 | 2×0.5 | 3.5 | 78.4 | 16452 | 0.093 | 3.5 | 505 | 515 |
State-of-in arte instrumenta Comperto.Bona nostra in USA, in UK et sic deinceps exportantur, stante superbo inter consumentes pro bono User famae pro 0.6/1kv Yjv22 Yjv23 Yjlv22 Yjlv23 XLPE Steel Tape Armored Underground Power Cable Insulated, ex omnibus vitae spatiis amicissime excepit. ut mutuam cooperationem petant et cras splendidiorem et splendidiorem efficiant.